S82H
S82H
3
Item
PFC
Yes
No
600 W
300 W
150 W
100 W
150 W
100 W
Other
Ambient temperature
Operating:
Storage:
25% to 85%
See the derating curve in the “Engineering Data” section. No condensation or icing.
–25
°
C to 65
°
C with no condensation or icing
Ambient humidity (operating)
Dielectric strength
3 kVAC, 50/60 Hz for 1 min between all inputs and all outputs with a current leakage of 25 mA max.
2.5 kVAC, 50/60 Hz for 1 min between all inputs and GR terminals with a current leakage of 25 mA
max.
1.0 kVAC, 50/50 Hz for 1 min between all outputs and GR terminals with a current leakage of 15 mA
max. for each 100-W model, 20 mA max. for each 150-W model, 25 mA max. for each 300-W
model, and 50 mA max. for each 600-W model. (See note 3.)
Insulation resistance
100 M
min. between all outputs and all inputs/GR terminals at 500 VDC (See note 3.)
Malfunction: 10 to 55 Hz, 0.375-mm single amplitude for 2 hrs each in X, Y, and Z directions
Malfunction: 300 m/s
2
(approx. 30G), 3 times each in
±
X,
±
Y, and
±
Z directions
Yes (green)
Vibration resistance
Shock resistance
Output indicator
EMC
Emission Enclosure:
EN55011 Group 1 class A (PFC models)
EN55022 Group 1 class B (Non-PFC models)
EN55011 Group 1 class A (PFC models)
EN55022 Group 1 class B (Non-PFC models)
EN61000-4-2:
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
ENV50140:
10 V/m (10 k to 1 GHz) (level 3)
ENV50141:
10 V (0.15 to 80 MHz) (level 3)
EN61000-4-4:
2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Emission AC Mains:
Immunity ESD:
Immunity RF-interference:
Immunity Conducted Disturbance:
Immunity Burst:
Limits for harmonic current
emission
EMC standards
---
Conforms to EN61000-3-2, IEC1000-3-2
Conforms to EN50081-1,
EN50082-2
Conforms to FCC class B
Conforms to EN50081-2, EN50082-2
Electromagnetic interference
Conforms to FCC class A
Approved standards
Weight
1. The fan is one of the replacement parts.
2. As defined with the rated input voltage and rated output voltage/current.
3. A surge absorber is provided for the input circuits of 300 and 600-W models. To test the dielectric strength and insulation resistance
of these models, remove the short bar attached across the GR and ACG terminals.
UL1012, CSA E.B. 1402C, VDE 0160, IEC 950, EN 60950
950 g max.
1,800 g max.
1,050 g max.
1,850 g max.
3,500 g max.
5,500 g max.
Note: