High Energy Industrial
HB34 Varistor Series
Varistor Products
86
www.littelfuse.com
Absolute Maximum Ratings
For ratings of individual members of a series, see Device Ratings and Specifications chart
Continuous:
Steady State Applied Voltage:
AC Voltage Range (VM(AC)RMS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130 to 750
DC Voltage Range (VM(DC)). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175 to 970
Transient:
Peak Pulse Current (ITM)
For 8/20μs Current Wave (See Figure 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40,000
Single Pulse Energy Range
For 2ms Current Square Wave (WTM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270 to 1050
Operating Ambient Temperature Range (TA). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -55 to 85
Storage Temperature Range (TSTG) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -55 to 125
Temperature Coefficient (
α
V) of Clamping Voltage (VC) at Specified Test Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . <0.01
V
V
A
J
O
C
O
C
%/
O
C
CAUTION: Stresses above those listed in “Absolute Maximum Ratings” may cause permanent damage to the device.This is a stress only rating and operation of the device
at these or any other conditions above those indicated in the operational sections of this specification is not implied.
Device Ratings and Specifications
HB34 SERIES UNITS
MODEL
NUMBER
SIZE
MAXIMUM RATINGS (85
o
C)
SPECIFICATIONS (25
o
C)
CONTINUOUS
TRANSIENT
VARISTOR VOLTAGE
AT 1mA DC TEST
CURRENT
MAXIMUM
CLAMPING
VOLTAGE
(V
C
) AT 200A
(8/20
μ
s)
TYPICAL
CAPACI-
TANCE
V
RMS
V
DC
ENERGY
(2ms)
PEAK
CURRENT
(8/20
μ
s)
V
M(AC)
V
M(DC)
W
TM
I
TM
MIN
V
N(DC)
MAX
V
C
f = 1MHz
(mm)
(V)
(V)
(V)
(A)
(V)
(V)
(V)
(V)
(pF)
V131HB34
34
130
175
270
40,000
184
200
228
345
10,000
V151HB34
34
150
200
300
40,000
212
240
268
405
8,000
V251HB34
34
250
330
370
40,000
354
390
429
650
5,000
V271HB34
34
275
369
400
40,000
389
430
473
730
4,500
V321HB34
34
320
420
460
40,000
462
510
561
830
3,800
V421HB34
34
420
560
600
40,000
610
680
748
1,130
3,000
V481HB34
34
480
640
650
40,000
670
750
825
1,240
2,700
V511HB34
34
510
675
700
40,000
735
820
910
1,350
2,500
V571HB34
34
575
730
770
40,000
805
910
1000
1,480
2,200
V661HB34
34
660
850
900
40,000
940
1050
1160
1,720
2,000
V751HB34
34
750
970
1050
40,000
1080
1200
1320
2,000
1,800
NOTE: Average power dissipation of transients not to exceed 2.0W.