3
www.power-one.com
Edition 5/07/01
S10079
6
10
14
18
22
26
30
4
8
12
16
20
24
28
32
Pin allocation
Pin
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
Electrical determination
Phase
Neutral
Protective earth
Protective earth
Output voltage positive
Output voltage positive
Hot plug-in contact, positive
Hot plug-in contact, negative
Output voltage negative
Output voltage negative
System good signal input
System good signal output
Inhibit input or remote control input
Power down signal
Power down signal threshold of U
o
Design.
P
N
Vo+
Vo+
HC+
HC
–
Vo
–
Vo
–
Sys In
Sys Out
i/U
cr
D
D set
T Series
500 Watt AC-DC Converters
EMC
Electrostatic discharge
Electromagnetic field
Electr. fast transients/bursts
Surge
Conducted disturbances
Electromagnetic emissions
IEC/EN 61000-4-2, level 4, contact/air
IEC/EN 61000-4-3, level 3
IEC/EN 61000-4-4, level 4, capacitive/direct
IEC/EN 61000-4-5, level 3
IEC/EN 61000-4-6, level 3
CISPR 22/EN 55022, conducted
8/15 kV, criterion A
10 V/m, criterion A
2/4 kV, criterion A
2 kV, criterion A
10 V
rms
, criterion A
class B
Environmental
Operating ambient temperature U
i nom
, I
o nom
, convection cooled
Operating case temperature T
C
U
i nom
, I
o nom
Storage temperature
Damp heat
Vibration, sinusoidal
Shock
Random vibration
MTBF
–
25...71
°
C
–
25...95
°
C
–
40...100
°
C
56 days
1.5 mm/5 g
n
100 g
n
4.9 g
n rms
198'000 h
non operational
IEC/EN 60068-2-3, 93%, 40
°
C
IEC/EN 60068-2-6, 2...28/28...2000 Hz
IEC/EN 60068-2-27, 6 ms
IEC/EN 60068-2-64, 20...500 Hz
MIL-HDBK-217E, G
B
, 40
°
C
Options
Remote bus voltage monitoring
Battery cell voltage selector switch
Mounting plate for chassis mounting
D
Z
B1