4
Operation
Remote Sensing Function
This function corrects a voltage drop in the load wiring. When using
the remote sensing function, remove the short bars from the remote
sensing terminals as shown in the following diagram.
Remote sensing connection
(2-wire shielded cable)
Load
Load wiring
Remove the
short bar
Note:
1. When the voltage drop in the load wiring is large, the
overvoltage protection function might engage just from
the increase in voltage to correct the voltage drop, so be
sure to use high capacity wiring.
2. If the +S and +V terminals are left unconnected, the high
voltage protection function will engage and the output
voltage will be cut off. If the -S and -V terminals are left
unconnected, the output voltage will increase about 5%.
Remote Control Function
This function allows the output voltage to be turned on and off with
an external signal (as long as the input voltage is being applied).
When using the remote control function, remove the short bar (at-
tached at ex-factory condition) from the remote control terminals
and connect a switch or transistor as shown in the diagram below.
Remove the
short bar
Tr*
*Use a transistor with V
CE
> 20
V and I
c
> 5 mA.
Level
Output voltage
L (0.8 V max.)
H (2 V min.)
Note:
ON
OFF
The remote control circuit is insulated from input, output,
and GR.
Fan Alarm
When the speed of the internal fan drops, the fan alarm output
(SPST-NO) will turn ON (shorted).
Normal condition
Alarm condition
Noise filter
Fuse*
ACG
FG
AC (L)
AC (N)
Input
100/200 V
Inrush
current
prevention
Rectifier
Rectifier
Drive
Detection
Overvoltage
detection
Low-voltage
detection
Fan alarm circuit
Remote control
circuit
Control circuit
Overload
detection
Auxiliary power
circuit
+ V
–
V
+ S
–
S
CB
FAN ALM
+ RC
–
RC
FAN ALM
DC Output
Remote sensing
Current balance
Fan alarm
Remote control
*Fuse capac-
ity
300 W: 8 A
600 W: 15 A
Short bar