Specifications are subject to change without notice (30.06.1999)
1
Type
Rated operational
voltage U
e
Rated operational
current I
e
Control voltage
U
c
*)
RSE: E-series,
motor controller
22: 127/220 VACrms, 50/60 Hz 03: 3 A
40: 230/400 VACrms, 50/60 Hz 12: 12 A
48: 277/480 VACrms, 50/60 Hz
60: 346/600 VACrms, 50/60 Hz
-B: 24 to 110 VAC/DC
& 110 to 480 VAC
*) The control voltage should never be higher than the rated operational voltage.
Solid State Relay
Motor controller
E-line housing
Rated operational voltage
Rated operational current
Control voltage
Ordering Key
Motor Controllers
AC Semiconductor Motor Controller
Types RSE 22 .. - B, RSE 4. .. - B, RSE 60 .. - B
RSE 40 03 - B
Soft starting and stopping of 3-phase
squirrel cage motors
Rated operational voltage: Up to 600 VACrms, 50/60 Hz
Rated operational current: 3 A or 12 AAC 53 b
Potential-free control input
LED-indications for supply and operation
Transient overvoltage protection built-in
Integral bypassing of semiconductors
Product Description
Type Selection
Input Specifications (Control Input)
Control voltage U
c
A1-A2:
24 - 110 VAC/DC ±15%,
12 mA
110 - 480 VAC ±15%,
5 mA
630 V rms
Overvoltage cat. III (IEC 60664)
A1-A3:
Rated insulation voltage
Dielectric strength
Dielectric voltage
Rated impulse withstand volt.
2 kVAC (rms)
4 kV (1.2/50 μs)
Output Specifications
Utilization catagory
AC-53b Integral bypassing
of semiconductors
Overload current profile
(overload relay trip class)
Min. load current
RSE ..03-B
RSE ..12-B
x/Tx: 6/13 (IEC 60947-4-2)
100 mAAC rms
200 mAAC rms
Compact easy-to-use AC
semiconductor motor con-
troller. With this controller 3-
phase motors with nominal
load currents up to 12 A can
be soft-started and/or soft-
stopped. Starting and stop-
ping time as well as initial
torque can be independently
adjusted by built-in potentio-
meters.