S uper-Lag Renewable Fuses
and Fuse Links
250 and 600 Volts, 1-600 Amps
REN and RES
(LK N & LK S )
Form No. REN/RES
Page 1 of 4
BIF Doc #1028
Bussmann
Designed for easy replacement.
No multiple links to complicate replacement.
Buss SUPER-LAG Renewable fuses with longer time-lag
than other Class H fuses of this type can better sustain over-
loads without needlessly opening.
SUPER-LAG fuses are used in circuits of industrial and
commercial structures where maximum short-circuit currents
are of a low level (below 10,000 amperes) and frequent out-
ages dictate the economy of the “renewable” type fuse.
These fuses are generally sized at the ampere rating of non-
inductive circuits and 300% for motor circuits.
1/10A to 30A
.56"
2"
35A to 60A
.81"
3"
70A to 100A
5.88"
450A to 600A
10.38"
225A to 400A
8.63"
110A to 200A
7.13"
Dimensional Data REN (250V)
450A to 600A
13.38"
225A to 400A
11.63"
110A to 200A
9.63"
1.06"
5.5"
35A to 60A
1/10A to 30A
0.81"
5"
70A to 100A
7.88"
Dimensional Data RES (600V)
CATALOG SYMBOLS: REN (250V); RES (600V)
TIME-LAG
1 TO 600 AMPERES
250 AND 600 VOLTS AC (OR LESS)
NON-CURRENT LIMITING
INTERRUPTING RATING–10,000A RMS SYM.
CLASS H
11-27-00
J00269