Specifications are subject to change without notice (09.12.05)
1
Monitoring Relays
3-Phase Active power
Types DWB02, PWB02
TRMS active power relays for three phase
balanced applications
Measuring if active power is within set limits
Measuring voltage on own power supply
Measuring ranges: 5A, 10A, MI current transformers
Power ON delay 1 to 30 s knob selectable
Separately adjustable upper/lower level on relative
scale
Programmable latching or inhibit at set level
Automatic and manual start and stop of the system
Output: 8 A SPDT relay N.D. or N.E. selectable
For mounting on DIN-rail in accordance with DIN/EN
50 022 (DWB02) or plug-in module (PWB02)
45 mm Euronorm housing (DWB02) or 36 mm plug-in
module (PWB02)
LED indication for relay, alarm and power supply ON
Product Description
DWB02 and PWB02 are
precise TRMS active power
monitoring relays for 3-
phase balanced systems.
They can be used for moni-
toring the actual load of
asynchronous motors and
other symmetrical loads, as
well as the power consump-
tion by of system.
Start/stop input allows to use
a manual switch to start and
stop the system, without the
need of an auxiliary device.
The advantage of using the
latch function is that the alarm
status can be kept even after
the end of the alarm condi-
tion. Inhibit function can be
used to avoid relay operation
when not desired (mainte-
nance, transitions).
The LED's indicate the state of
the alarm and the output relay.
Input Specifications
Input
Voltage (Own power supply):
3 - phase
DWB02:
PWB02:
M23:
L1, L2, L3
5, 6, 7
208 to 240 VAC ± 15%
380 to 480 VAC ± 15%
380 to 415 VAC ± 15%
600 to 690 VAC ± 15%
L1, L2
5, 6
208 to 240 VAC ± 15%
5A, 10A: I1, I2
MI...:U1, U2
5A, 10A: 11, 10
MI...: 9, 8
Upper level
10 to 110 %
AACrms
DWB02CM48:
PWB02CM48:
DWB02CM69:
DWB02CM23:
PWB02CM23:
1- phase
Current:
DWB02:
PWB02:
Measuring ranges
Active power
Lower level
10 to 110 %
Max. curr.
(30s)
30A
50A
Direct input:
0.5 to 5A
1 to 10A
Standard CT (examples)
TADK2 50 A/5 A
TAD2 150 A/5 A
TAD6 400 A/5 A
TAD12 1000 A/5 A
TACO200 6000 A/5 A
MI CT ranges
MI 100
MI 500
Note:
The input voltage cannot
raise over 300 VAC with
respect to ground (PWB02
only)
Contact input
DWB02
PWB02
Disabled
Enabled
Pulse width
Hysteresis
5 to 50 A
15 to 150 A
40 to 400 A
100 to 1000 A
600 to 6000 A
60 A
180 A
480 A
1200 A
7200 A
10 to 100 A
50 to 500 A
250 AAC
750 AAC
Terminals Z1, U2
Terminals 2, 9
> 10 k
< 500
> 500 ms
~ 2% of set value - fixed
DWB02
PWB02
Ordering key
Housing
Function
Type
Item number
Output
Power Supply
Range
DWB 02 C M48 10A
Type Selection
Mounting
Output
Supply:
208 to 240 VAC
Supply:
380 to 415 VAC
Supply:
380 to 480 VAC
Supply:
600 to 690 VAC
DIN-rail
Plug-in
SPDT
SPDT
DWB 02 C M23 10A
PWB 02 C M23 10A
DWB 02 C M48 10A
DWB02 C M69 10A
PWB 02 C M48 10A