2
Specifications are subject to change without notice (15.09.05)
DAC01, PAC01
Supply Specifications
General Specifications
Power supply
Rated operational voltage
through terminals:
A1 and A2
2, 10
Overvoltage cat. III
(IEC 60664, IEC 60038)
(DAC01)
(PAC01)
M24
24 to 240 VAC/DC
+10% -15%, 45 to 65 Hz
380 to 415 VAC
+10% -15%, 45 to 65 Hz
≤
10 ms
M40:
Voltage interruption
Rated operational power
M24
AC Supply:
DC Supply:
AC Supply:
4 VA
1.5 W
13 VA @ 400 VAC, 50 Hz
M40
Power ON delay
Power OFF delay
Indication for
Power supply ON
Output relays ON
≤
100 ms
≤
100 ms
LED, green
LED, yellow (flashing when
timing)
(EN 60529)
IP 20
3 (DAC01) ,2 (PAC01)
(IEC 60664)
-20 to 60 °C, R.H. < 95%
-30 to 80 °C, R.H. < 95%
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Housing dimensions
DIN-rail version
Plug-in version
Weight
Screw terminals
Tightening torque
22.5 x 80 x 99.5 mm
36 x 80 x 94 mm
Approx 110 g
DAC01
Max 0.5 Nm according to
IEC EN 60947
UL, CSA
Yes
Electromagnetic Compatibility
According to EN 61000-6-2
According to EN 61000-6-3
According to EN 61812-1
Approvals
CE Marking
EMC
Immunity
Emission
Timer Specifications
Mode of Operation
The output relay is normally
in the neutral centre position.
When the power supply is
applied, the relay switches to
star position (pin 16 or 4)
and the star period starts.
At the end of the set time
period, the relay returns to
the neutral centre position
and the set delay between
star and delta position starts.
At the end of the star to
delta delay (adjustable from
50 to 130 ms), the relay
switches in delta position
(pin 18 or 3) and does not
release until the power sup-
ply is interrupted for at least
200 ms.
If the power supply is inter-
rupted for more than 200 ms
before the star time period
has expired, the relay does
not operate and the time cir-
cuit is set to zero. The relay is
ready for a new time period.
Time Setting
Upper knob:
Setting of star time range
Centre knob:
Star time setting on relative
scale: 1 to 10 with respect
to the chosen range.
Lower knob:
Star to delta time setting (50
to 130 ms)
Wiring Diagrams
L(+)
N(-)
A1
15
16
18
A2
L(+)
N(-)
2
1
4
3
10
DAC01
PAC01