Cassette Style
150 Watt AC-DC Converters
K Series
Edition 01/01.2001
5/26
Input Inrush Current Characteristic
1
23
t [ms]
0
50
100
Iimp [A]
130
04050
Fig. 6
Inrush current versus time at Ui max, Rext = 0
Hold-up Time versus relative Input Voltage
23
4
5
6
1
2.00
U
i AC
_______
U
i min AC
t
h (ms)
10.00
100.00
04049
Fig. 5
Hold-up time th versus relative input voltage Ui/Ui min.
Input Transient Protection
A VDR together with the input fuse and a symmetrical input
filter form an effective protection against high input tran-
sient voltages.
Electrical Output Data
General Conditions
–
TA = 25°C, unless TC is specified.
– Pin 18 (i) connected to pin 14 (S–/Vo1–),
Uo adjusted to Uo nom (option P), R input not connected.
– Sense line pin 12 (S+) and pin 14 (S–) connected to pin 4 (Vo+) and pin 8 (Vo–) respectively.
Table 4a: Output data single output modules
Output
LK 1001
LK 1301
LK 1501
LK 1601
5.1 V
12.0 V
15.0 V
24.0 V
Characteristics
Conditions
min
typ
max
min
typ
max
min
typ
max
min
typ
max
Unit
Uo
Output voltage
Ui nom, Io nom
5.07
5.13
11.93
12.07 14.91
15.09 23.86
24.14
V
Uop
Overvoltage protection
7.6
21
26.5
43.5
(supressor diode)
Io nom
Output current 1
Ui min...Ui max
25.0
12.0
10
6.0
A
TC min...TC max
IoL
Output current limit 4
Ui min...Ui max
26
12.2
10.2
6.2
uo 7
Output
Low frequency
Ui nom, Io nom
5
555
mVpp
voltage
Switching freq.
IEC/EN 61204
5
555
noise
Total
BW = 20 MHz
50
70
60
90
DUo U
Static line regulation
Ui min...Ui nom,
±15
±25
±30
±30 mV
Ui nom...Ui max,
Io nom
DUo I
Static load regulation
Ui nom, Io =
202530
40
(0.1...1)
Io nom
uo d 5
Dynamic Voltage
Ui nom, Io =
±100
±80
load
deviation
Io nom 1/2 Io nom
td 5
regulat.
Recovery time
IEC/EN 61204
0.3
0.4
ms
aUo
Temperature coefficient
Ui min...Ui max
–1
–1mV/K
of output voltage 6
0...
Io nom
1 If the output voltages are increased above Uo nom through R-input control, option P setting, remote sensing or option T, the output cur-
rents should be reduced accordingly so that
Po nom is not exceeded.
4 See: Output Voltage Regulation of Single Output Units or Double Output Modules with Outputs 1 and 2 Connected in Series.
5 See: Dynamic load regulation of Uo1 and Uo2.
6 Negative temperature coefcient (0...–3 mV/cell and K) available on request.
7 Measured according to IEC/EN 61204 sub clause 3.10 with a probe acc. to annex A of the same standards. (See:Technical Informa-
tion: Measuring and Testing)