Electrical data
Primary nominal
current
I
PN
(A)
Primary current
measuring range
I
P
(A)
Type
4000
6000
10000
12000
14000
20000
±
4000
±
6000
±
10000
±
12000
±
14000
±
20000
HAZ 4000-SRI
HAZ 6000-SRI
HAZ 10000-SRI
HAZ 12000-SRI
HAZ 14000-SRI
HAZ 20000-SRI
V
C
I
C
I
OC
V
d
V
b
R
IS
I
OUT
R
OUT
R
L
Supply voltage (± 5 %)
Current consumption
Overload capacity
R.m.s. voltage for AC isolation test, 60 Hz, 1 mn
R.m.s. rated voltage, safe separation
Isolation resistance @ 500 VDC
Output current @ ±
I
,
T
A
= 25°C
Output internal resistance
Load resistance
± 15
± 50 mA
30,000
12
2000
1)
> 1000
0-20
V
At
kV
V
M
mA DC
approx. 20
< 300
Accuracy - Dynamic performance data
X
e
L
I
OE
I
OM
Accuracy @
I
,
T
A
= 25°C (without offset)
Linearity
2)
(0 .. ±
I
)
Electrical offset current,
T
A
= 25°C
Residud offset current @
I
P
= 0;
after an excursion of 1 x
I
PN
Thermal drift of
I
Thermal drift of the gain (% of reading)
Arranging time constant
Frequency bandwidth
3)
(- 3 dB)
< ± 1
< ± 1
< ± 0.08
%
% of
I
mA
< ± 0.025
<
± 0.05 %of
I
/K
< ± 0.05
< 400
DC .. 3
mA
I
TC
e
G
t
r
f
%/K
ms
kHz
General data
T
A
T
S
m
Ambient operating temperature
Ambient storage temperature
Mass
Standards
4)
Minimum creepage & clearance
Housing PBT 30% glassfiber
- 10 .. + 80
- 25 .. + 80
°C
°C
kg
approx. 6
EN 50178
45
CTI IIIa, UL94-V0
mm
Current Transducers HAZ 4000..20000-SRI
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
I
PN
I
OUT
= 0 - 20 mA
= 4000..20000 A
Features
Hall effect measuring principle
Galvanic isolation between primary
and secondary circuit
True-rms, 0-20mA DC current output
Isolation voltage 12kV~
Low power consumption
Package in PBT meets UL 94-V0
Advantages
Easy mounting
Small size and space savings
Only one design for wide current
ratings range
High immunity against external
interference
Applications
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Power supplies for welding and
telecommunication applications.
Notes :
1)
Pollution class 2, overvoltage category III, reinforced insulation
2)
Linearity data exclude the electrical offset.
3)
Please refer to derating curves in the technical file to avoid excessive
core heating at high frequency
4)
Please consult characterisation report for more technical details and
application advice.
040713/0
LEM Components
www.lem.com
Preliminary