Multifunction Preset Counter
H7CX (Counter Function)
C-115
C
Note: 1.
Counting cannot be performed during reset/reset 1 input.
2.
If reset/reset 1 is input while one-shot output is ON, one-shot output turns OFF.
3.
If there is power failure while output is ON, output will turn ON again when the power supply has recovered. For one-shot output, output
will turn ON again for the duration of the output time setting once the power supply has recovered.
4.
Do not use the counter function in applications where the count may be completed (again) while one-shot output is ON.
Input mode
UP/DOWN A, B, C
Operation after count
completion
Output
mode
setting
K-2
The display continues to in-
crease/decrease until the over-
flow or underflow value is
reached. One-shot output only.
D
The display continues to in-
crease/decrease until the over-
flow or underflow value is
reached. The outputs are ON
while the count is equal.
L
crease/decrease until the over-
flow or underflow value is
reached.
OUT1 is held while the present
value is less than or equal to set
value 1. OUT2 is held while the
present value is greater than or
equal to set value 2.
H
The display continues to in-
crease/decrease until the over-
flow or underflow value is
reached.
OUT1 is held while the present
value is greater than or equal to
set value 1. OUT2 is held while
the present value is greater than
or equal to set value 2.
Note:
H mode is available only when
using a 6-digit model as a 2-
stage counter.
(The one-shot output time
can be set in the range 0.01
to 99.99s.)
Self-holding
output
Instantaneous
(equals) output
One-shot
output
0
999999
Set
value 2
Set
value 1
99999
OUT1
OUT2
Reset/
reset 1
0
999999
Set
value 2
Set
value 1
99999
OUT1
OUT2
Reset/
reset 1
0
999999
Set
value 2
Set
value 1
99999
OUT1
OUT2
Reset/
reset 1
0
999999
value 2
Set
value 1
99999
OUT1
OUT2
Reset/
reset 1