B-112
Solid-state Multi-functional Timer
H3CR-A
I
Time Ranges
Note:
When the time setting knob is turned below
“
0
”
until the point where the time setting knob stops, the output will operate instantaneously at
all time range settings.
Standard (0.05-s to 300-h) Models
Double (0.1-s to 600-h) Models
I
Ratings
Note: 1.
DC ripple rate: 20% max. if the power supply incorporates a single-phase, full-wave rectifier.
2.
Each 24-to-48-VAC/12-to-48-VDC model causes an inrush current of approximately 0.85 A. Pay careful attention when attempting to turn
ON power to such a model with non-contact output from a device such as a sensor.
3.
The values are for when the terminals 2 and 7 and terminals 10 and 6 are short-circuited, and include the consumption current of the
input circuit.
Time unit
s (sec)
min (min)
h (hrs)
x10 h (10 h)
Full scale set-
ting
1.2
3
12
30
0.05 to 1.2
0.3 to 3
1.2 to 12
3 to 30
0.12 to 1.2
1.2 to 12
3 to 30
12 to 120
30 to 300
Time unit
s (sec)
min (min)
h (hrs)
x10 h (10 h)
Full scale set-
ting
2.4
6
24
60
0.1 to 2.4
0.6 to 6
2.4 to 24
6 to 60
0.24 to 2.4
2.4 to 24
6 to 60
24 to 240
60 to 600
Rated supply voltage (see note 1)
100 to 240 VAC (50/60 Hz)/100 to 125 VDC, 24 to 48 VAC (50/60 Hz)/12 to 48 VDC (24 to 48 VAC/VDC for H3CR-
A8E) (see note 2)
85% to 110% of rated supply voltage (90% to 110% at 12 VDC)
Minimum power-opening time: 0.1 s
No-voltage Input
ON impedance:
1 k
max.
ON residual voltage:
1 V max.
OFF impedance:
100 k
min.
Voltage Input
Max. permissible capacitance between inputs lines (terminals 6 and 7): 1,200 pF
Load connectable in parallel with inputs (terminals 6 and 7).
100 to 240 VAC/100 to 125 VDC
High (logic) level:
85 to 264 VAC/85 to 137.5 VDC
Low (logic) level:
0 to 10 VAC/0 to 10 VDC
24 to 48 VAC/12 to 48 VDC
High (logic) level:
20.4 to 52.8 VAC/10.8 to 52.8 VDC
Low (logic) level:
0 to 2.4 VAC/0 to 1.2 VDC
H3CR-A/-A8
100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON: approx. 2.0 VA (1.6 W)
24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Relay ON: approx. 0.8 W
H3CR-AP (see note 3)
100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON: approx. 2.5 VA (2.2 W)
24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Relay ON: approx. 0.9 W
H3CR-A8E
100 to 240 VAC/100 to 125 VDC
(When at 240 VAC, 60 Hz)
Relay ON/OFF: approx. 2 VA (0.9 W)
24 to 48 VAC/VDC
(When at 24 VDC)
Relay ON/OFF: approx. 0.9 W
H3CR-AS/-A8S
24 to 48 VAC/12 to 48 VDC
(When at 24 VDC)
Output ON: 0.3 W Output OFF: 0.2 W
Time limit contacts:
5 A at 250 VAC/30 VDC, 0.15 A at 125 VDC, resistive load (cos
φ
= 1)
Transistor output:
Open collector (NPN/PNP), 100 mA max. at 30 VDC max.,
residual voltage: 2 V max.
Instantaneous contact:
5 A at 250 VAC/30 VDC, 0.15 A at 125 VDC, resistive load (cos
φ
= 1)
Operating voltage range
Power reset
Input
Power consumption
Relay OFF: approx. 1.3 VA (1.1 W)
Relay OFF: approx. 0.2 W
Relay OFF: approx. 1.8 VA (1.7 W)
Relay OFF: approx. 0.3 W
Control outputs