Specifications are subject to change without notice (27.10.99)
H 211
Power ON time
Power OFF delay
Indication for
Power supply ON
Output ON
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Weight
≤
200 ms
≥
200 ms
LED, green
LED, red
IP 20 B/front IP 40 D
3 (IEC 60664)
-20° to +50°C (-4° to +122°F)
-50° to +85°C (-58° to +185°F)
100 g
Power supply AC type
Rated operational voltage
through term. 21 & 22
Installation cat. III (IEC 60664)
230
115
230 VAC ± 15%, 45-65 Hz
115 VAC ± 15%, 45-65 Hz
24 VAC +15/-10%, 45-65 Hz
≥
40 ms
None
or term. 21 & 3
Drop-out tolerance
Rated insulation voltage
Rated transient protection volt. 4 kV (1.2/50 μs)
(line/neutral)
Installation cat. III (IEC 60664)
Power supply DC type
Rated operational voltage
through term. 21 & 3
Rated insulation voltage
Rated transient protection volt. 800 V (1.2/50 μs)
Consumption
AC supply
230
24 VDC +15/-10% - term. 3: +
None
30 mA @ 50 Hz/
40 mA @ 60 Hz
1 W
DC supply
Mode of Operation
Function 1
Delay on operate
No connection between the
terminals.
The delay period begins when
power supply is applied.
At the end of the set delay,
the relay will operate and will
not release until power sup-
ply is interrupted.
A recovery period of 200 ms
should be allowed before
reapplying power supply.
If power supply is interrupted
for more than 200 ms before
the relay operates, the time
circuit is reset to zero and the
time relay is ready for a new
time period.
Function 2
Interval timer
Connection between termi-
nals 1 and 2.
The relay operates and the
time period starts when power
supply is applied to the time
relay.
At the end of the set delay,
the relay releases and will not
operate again until power
supply is reapplied.
A recovery period of 200 ms
should be allowed before
reapplying power supply.
If power supply is interrupted
for more than 200 ms before
the time period has expired,
the relay releases and the time
is reset to zero.
Function 3
Interval timer
with time reset
Power supply must be con-
stantly applied. When inter-
connecting terminals 1 and 2
the relay will operate.
When terminals 1 and 2 are
disconnected, the time pe-
riod starts, and when the pe-
riod has expired, the relay
releases.
When interconnecting termi-
nals 1 and 2 before the delay
period has expired, the time
is reset to zero and the time
period restarts when the in-
terconnection between termi-
nals 1 and 2 is interrupted.
Wiring Diagram
Accessories
For further information refer
to "Accessories".
Time Setting
Knob-adjustable on relative
scale (1-10).
Left knob on housing:
Selection of time range (sec-
onds, minutes, hours).
Operation Diagram
Centre knob on housing:
Time range multiplicator x 0.1
and x 1.
Right knob on housing:
Selection of functions.
Power supply
Reset (intercon. 1 & 2)
Function 1. Relay on
Function 2. Relay on
Function 3. Relay on
Power supply
24 VAC/DC
Reset
Power supply - 230 VAC
For other AC/DC voltages
refer to "General Informa-
tion".
Supply Specifications
General Specifications