Precautions
I
HANDLING
To preserve performance, do not drop or otherwise subject
the G7J relay to shock.
The case is not designated to be removed during normal
handling and operation. Doing so may affect performance.
Use the power relay in a dry environment free from
excessive dust, SO
2
, H
2
S, or organic gas.
Do not allow a voltage greater than the maximum allowable
coil voltage to be applied continuously.
Do not use the relay outside of specified voltages and
currents.
Do not allow the ambient operation temperature to exceed
the specified limit.
I
INSTALLATION
Although there are not specific limits on the installation site, it
should be as dry and dust-free as possible.
PCB terminal-equipped relays weigh approximately 140 g. Be
sure that the PCB is strong enough to support them. OMRON
recommends dual-side through-hole PCBs to reduce solder
cracking from heat stress.
I
APPROVALS
UL 508 and 1950 (Recognized, File No. E41643)/CSA 22.2 No. 14 (Certified, File No. LR 35535)
Contact arrangement
Normally Open
Load type
Resistive
Contact ratings
25 A, 277 VAC, 30,000 cycles
25 A, 30 VDC, 30,000
25 A, 120 VAC, 30,000 cycles
25 A, 277 VAC, 30,000 cycles
25 A, 240 VAC, 100,000 cycles
1.5 kW, 120 VAC
1.5 HP, 120 VAC
3 HP, 240/265/277 VAC
3-phase, 3 hp, 240/265/277 VAC, 30,000 cycles
3-phase, 5 hp, 240/ 265/277 VAC, 30,000 cycles
20 FLA/120 LRA, 120 VAC, 30,000 cycles
17 FLA/102 LRA, 277 VAC, 30,000 cycles
TV-10, 120 VAC
8 A, 277 VAC, 30,000 cycles
8 A, 30 VDC, 30,000 cycles
8 A, 120 VAC, 30,000 cycles
8 A, 277 VAC, 30,000 cycles
General use
Tungsten
Motor load
TV
Resistive
Normally Closed
General use
Note:
1. The rated values approved by each of the safety standards may be different from the performance characteristics
individually defined in this catalog.
2. In the interest of product improvement, specifications are subject to change without notice.
I
CLEANING PCB TERMINALS
PCB terminals have semi-sealed construction which prevents
flux from penetrating into the relay base housing due to
capillary action. This type of relay cannot be immersed for
cleaning.
I
CONNECTION
Refer to the diagram below when connecting a wire to the
screw terminals on G7J.
Allow suitable slack on leads when wiring, and do not subject
the terminals to excessive force. Maximum tightening torque is
10 kgf-cm (72.50 ft-lbs).
M3.5
7 (0.276)
4.5
(0.177)
7.6
(0.299)
8.8
(0.346)