參數資料
型號: FN3410-110-35
元件分類: 電源濾波器
英文描述: 500 V, 50 HZ, THREE PHASE EMI FILTER
封裝: ROHS COMPLIANT PACKAGE
文件頁數: 4/16頁
文件大?。?/td> 3480K
代理商: FN3410-110-35
ECOsine
Typical electrical schematic
Filter*
Rated load power
Filter efficiency
Input/Output
Capacitor
Weight
@ 400VAC/50Hz
@ 500VAC/50Hz
@ 25°C/50Hz
connections
disconnections
[kW]
[%]
[kg]
Filter selection table
FN 3410-10-44
4
5.5
98.5
–44
13
FN 3410-13-44
5.5
7.5
98.5
–44
14
FN 3410-16-44
7.5
11
98.5
–44
21
FN 3410-24-33
11
15
98.5
–33
–44
27
FN 3410-32-33
15
18.5
98.5
–33
–44
31
FN 3410-38-33
18.5
22
98.6
–33
–44
35
FN 3410-45-34
22
30
98.7
–34
–33
45
FN 3410-60-34
30
37
98.8
–34
–33
54
FN 3410-75-35
37
45
98.9
–35
–34
65
FN 3410-90-35
45
55
99.0
–35
–34
77
FN 3410-110-35
55
75
99.1
–35
–34
86
FN 3410-150-40
75
90
99.2
–40
–35
118
FN 3410-180-40
90
110
99.3
–40
–35
136
FN 3410-210-40
110
132
99.3
–40
–35
154
FN 3410-260-99
132
160
99.4
–99
–35
201
*
Filter to be selected by system voltage and load (motor drive) power. Note: the harmonic filter will reduce the RMS input current. Example: the rated RMS input current of an unfiltered
400V/15kW/32A drive will be reduced to approximately 23A. Therefore, filter selection by current rating, as it is common for EMI filters, is not suitable.
Technical specifications
Nominal operating voltage:
3x 380 to 500VAC
Voltage tolerance range:
3x 342 to 550VAC
Operating frequency:
50Hz ±1Hz
Nominal motor drive input current rating*:
10 to 260A @ 50°C
Nominal motor drive input power rating:
4 to 160kW
Total harmonic current distortion THID**:
<5% @ rated power
Total demand distortion TDD:
According to IEEE-519, table 10-3
Efficiency:
>98.5% @ nominal line voltage and power
High potential test voltage:
P –> E 2500VAC (1min)
Protection category:
IP20 / NEMA1
Cooling:
Internal fan cooling
Overload capability:
1.6x rated current for 1 minute, once per hour
Ambient temperature range:
–25°C to +50°C fully operational
+50°C to +70°C derated operation***
–25°C to +85°C transport and storage
Flammability corresponding to:
UL 94V-2 or better
Design corresponding to:
UL 508, EN 61558-2-20, CE (LVD 2006/95/EC)
MTBF @ 50°C/500V (Mil-HB-217F):
200,000 hours
*
ECOsine filters reduce RMS input and peak current by reducing harmonic currents and improving true power factor.
**
System requirements: THVD < 2%, line voltage unbalance < 1%
*** I
derated = Inominal * √(85°C-Tamb)/35°C
2
ECOsine FN 340 – filters for 50Hz systems
Line
Power capacitors
Trap choke
In-Out choke
Power
supply
Fan
Control
error
red
PE
L3
L2
L1
L3'
NC
C
L2'
L1'
A1
B1
C1
A2
B2
C2
yellow
green LED
cooling power on
Disconnect
Load
Monitor
EUT
EMI
EUT
EMI
Equipment under test
EMI receiver
GP Ground plane
Height variable 1 - 4m
GP
Direct wave
Ground reflected wave
相關PDF資料
PDF描述
FN3410-13-44 500 V, 50 HZ, THREE PHASE EMI FILTER
FN3410-150-40 500 V, 50 HZ, THREE PHASE EMI FILTER
FN3410-16-44 500 V, 50 HZ, THREE PHASE EMI FILTER
FN3410-180-40 500 V, 50 HZ, THREE PHASE EMI FILTER
FN3410-210-40 500 V, 50 HZ, THREE PHASE EMI FILTER
相關代理商/技術參數
參數描述
FN3410-150-40 制造商:Schaffner 功能描述:
FN3410-16-44 制造商:Schaffner 功能描述:
FN3410-24-33 制造商:Schaffner 功能描述:
FN3410-45-34 制造商:Schaffner 功能描述:
FN3412-240-99 制造商:Schaffner 功能描述:Schaffner Ecosine harmonic Filter