F3M-S
F3M-S
7
J F3M-S1213
J F3M-S1225
Optical axis
Two, M4, depth: 8
(mounting holes)
OMRON XG4A-3034
Connector
Teaching button
RUN/TEACH mode selector
Warning indicator
Teaching indicator
Power indicator
Optical axis
Optical axis
Two, M4, depth: 8
(mounting holes)
OMRON XG4A-3034
Connector
Teaching button
RUN/TEACH mode selector
Warning indicator
Teaching indicator
Power indicator
Optical axis
Optical axis
Optical axis
50
(1.97)
140 (5.51)
25 (0.98)
18 (0.71)
50
(1.97)
260 (10.24)
25 (0.98)
18 (0.71)
Precautions
J CORRECT USE
Avoid Damage to the F3M-S
"  Do not use the F3M-S at a voltage that exceeds the rated
voltage range.
"    Do not make mistakes in wiring, such as mistakes in polarity.
"    Do not short-circuit the load.
"    Do not connect AC to the F3M-S.
J INSTALLATION/ENVIRONMENT
Do NOT use the F3M-S in the following places:
"    Places exposed to direct sunlight.
"    Places with high humidity that may cause condensation.
"    Places with corrosive gas.
"    Places with vibration or shock directly affecting the Sensor.
J CONNECTION AND MOUNTING
"    A maximum of 24 VDC+10% can be imposed on the F3M-S.
Check that the voltage of the power supply is within the per-
missible range before turning on the F3M-S. The power sup-
ply must be constructed so that the secondary circuit is insu-
lated with an isolating transformer.
"    Do not wire power lines or high-tension lines within the same
conduit with the lines of the F3M-S, or the F3M-S may be
damaged or malfunction due to induction. You must wire the
lines of the F3M-S separate from power lines or high-tension
lines or laid in an separate, shielded conduit.
"    Avoid mechanical impact when mounting the F3M-S, or the
water-resistant properties of the F3M-S will be reduced.
J CLEANING
Do not attempt to clean the F3M-S using paint thinner, to avoid
damaging the surface of the F3M-S.
J POWER SUPPLY
If a standard switching power supply is connected to the F3M-S,
be sure to ground the FG (frame ground) and G (ground)
terminals of the power supply. The F3M-S may malfunction due
to switching noise that will be generated from the power supply if
these terminals are not grounded.