Specifications are subject to change without notice (20.07.06)
1
Product Description
Interval
Type EBS
Small, low cost monofunc-
tion timer with adjustable
time setting. 2-wire connec-
tion for easy and fail-safe
use
(see
diagram).
mounting on DIN-rail or
For
directly on surface by screw.
The timer is used e.g. with
industrial relays or 3-phase
contactors.
Fail-safe two-wire connection
Low-cost
Multi-voltage: 24-230 VAC
Interval timer
Time range: 0,5 s - 10 m
Knob-adjustable time setting
Output: SCR 10-500 mA (screws) and SCR 10-700mA
(Fast-ON)
For mounting on DIN-rail in accordance with
DIN/EN 50 022
22,5 mm small Euronorm housing
Timers
Ordering Key
Housing
Function
Small E-line
Output
Power supply
Time range
Fast-ON connection
Type Selection
Mounting
Output
Time range
Connection
Supply: 24 - 230 VAC
For DIN-rail
or for screw
SCR
SCR
SCR
0.5 - 10 s
0.1 -1 m
1 - 10 m
Screws
Screws
Screws
EBS S M23 10S
EBS S M23 1M
EBS S M23 10M
For DIN-rail
or for screw
SCR
SCR
SCR
0.5 - 10 s
0.1 -1 m
1 - 10 m
Fast-ON
Fast-ON
Fast-ON
EBS S M23 10S F
EBS S M23 1M F
EBS S M23 10M F
EBS S M23 10S F
Time Specifications
Time ranges
10 s
1 m
10 m
Time range accuracy
0.5 - 10 s
0.1 - 1 m
1 - 10 m
Max. setting: actual time
≥
max. set time
min. setting: actual time
≤
min. set time
≤
0.2%
Repeat accuracy
Time variation
Within rated power supply
and ambient temperature
Reset
Time and output
≤
0.1%/V
≤
0.2%/°C
Power supply interruption
≥
200 ms
Output Specifications
Output
Output current
Maximum load current
(screw terminals)
(Fast-ON connection)
Maximum current for 100 ms
(screw terminals)
(Fast-ON connection)
Minimum load current
Leakage current
SCR
500 mA
700 m
5.5 A
7 A
10 m
≤
3.5 mA @ 230 V
typ.: 2 m
≤
8 VAC
typ.: 5 VAC @ 50 mA
Voltage drop
Supply Specifications
Power supply
Rated operational voltage
Overvoltage cat. III (IEC 60664)
(IEC 60038)
24-230 VAC, -10/+15%
None
Rated insulation voltage
SCREW
FASTON