CVR375-96D56
AC/DC power supply
for disk storage systems
365 Watt, dual output : +12, +5VDC
[ 2 YEAR WARRANTY ]
Universal input voltage range
EN61000-3-2 compliant for power factor and
line harmonics
UL and T
ü
V safety agency approvals
Short circuit protection
Overtemperature protection (auto recovery)
Overvoltage protection
Remote sensing of outputs
Warm-swappable operation
N+1 redundancy / parallel operation
FCC and CISPR Class B conducted noise compliant
FCC and CISPR Class A (stand-alone) / Class B (system)
radiated noise compliant
AC line fusing
250,000 hour MTBF
4.9 x 9.0 x 3.6 inches (W x D x H) - suitable for
3U applications
SPECIFICATION
All specifications are typical at nominal input, full load at 25
°
C unless otherwise stated
SPECIFICATIONS
Input voltage
Low range
High range
90 to 132VAC
180 to 264VAC
Input frequency range
50/60Hz
Power factor
(full load)
Low range
High range
>0.98
>0.96
Inrush current
Low range
High range
22A
40A
Hold-up time
20ms
Output voltage
(initial tolerance)
+12V
+5V
+5V auxiliary
12.15VDC ±1.0%
5.10VDC ±1.0%
5.00VDC ±1.0%
Output ratings
+12V (steady-state)
+12V (30s pk, 10% duty)
+5V
+5V auxiliary
22A
28A
20A
30mA
Output regulation
+12V
+12V (peak)
+5V
+5V auxiliary
±2.0%
+2.0%/-3.0%
±2.0%
±1.0%
Ripple and noise
+12V
+12V (peak)
+5V
+5V auxiliary
120mV pk-pk
200mV pk-pk
50mV pk-pk
50mV pk-pk
Current share
+12V, +5V
±10%
Remote sense
compensation
+12V, +5V
100mV
Efficiency
Full load
Half load
>73%
>70%
Thermal performance
Operating ambient
0°C to +50°C
NEW
The CVR375 power supply is designed for storage/networking RAID
applications. The power supply has an integrated 80mm fan for
internal cooling and or-ing diodes on each output to provide output
isolation. The power supplies are designed for parallel operation
and are warm-swappable. It is recommended that the AC power
for a supply be removed during extraction/insertion to minimize
disturbance on the main output bus for redundant systems. The
power supplies are designed for mounting within standard 19 inchs
shelves or rack-mount systems.
Control and indicator signals:
CSIN1 (12V current share pin)
CSIN2 (5V current share pin)
VS1+ (positive 12V remote sense)
VS1- (negative 12V remote sense)
VS2+ (positive 5V remote sense)
VS2- (negative 5V remote sense)
PS_ENABLE (main outputs remote enable)
PSU_FAIL (undervoltage for main outputs)
ACOK (AC input status)
DISCONNECT (auto disable/enable provision for
extraction/insertion)
PSU_FAIL LED
AC_OK LED