4
Specifications are subject to change without notice CPT-DINADS110706
CPT-DIN
AC/DC voltage
90 to 260VAC/DC
18 to 60VAC/DC
Power consumption
AC: 2.5 VA
DC: 2W
Pow er Supply Specifications
4kVAC
between
power supply and
RS485/RS232/programming
port (RJ 12)
4kVAC
RMS
(for 1 min)
Dielectric strength
EMC
Emissions
EN61000-6-3, EN60688
residential environment,
commerce and light industry
EN61000-6-2
industrial environment.
EN61000-4-5
IEC60664, IEC61010-1
EN60664, EN61010-1
IEC60688, EN60688,
EN62053-31, EN62053-23
CE, cURus
Screw-type
2.5 mm
2
Immunity
Pulse voltage (1.2/50μs)
Safety standards
Mesurement standards
Approvals
Connections 5(6) A
Max cable cross sect. area
Housing
Dimensions (WxHxD)
Material
45 x 83.5 x 98.5 mm
ABS
self-extinguishing: UL 94 V-0
DIN-rail
IP20
Approx. 200 g (pack. incl.)
Mounting
Protection degree
Weight
Front LED’s
Power on
Diagnostics
Green
RS485/RS422/RS232
TX data (Green)
RX data (Red)
TX data (Green)
RX data (Red)
1st output activation (Green)
2nd output activation (Red)
1st output activation (Green)
2nd output activation (Red)
Output signal within the
programmed scale (Green)
Output signal exceeding
110% of full scale (Red)
0° to +50°C (32° to 122°F)
(RH < 90% non condensing)
-10° to +60°C (14° to 140°F)
(RH < 90% non condensing)
Cat. III (IEC 60664, EN60664)
4kVAC
RMS
between measuring
inputs and power supply.
4kVAC/DC @I
≥
3mA
between measuring inputs
and RS485/RS232/
programming port (RJ 12)
Dupline bus
Alarm outputs
Pulse outputs
Analogue outputs
Operating
temperature
Storage
temperature
Overvoltage category
Insulation
(for 1 minute)
General Specifications
- W dmd max, VA dmd max,
A
1
max, A
2
max, A
3
max,
W
max, W
max, W
max,
W sys max, A
1
dmd max,
A
2
dmd max, A
3
dmd max,
VA sys dmd max,
W sys dmd max, PF
1
min,
PF
2
min, PF
3
min
- all the counters: total kWh,
partial kWh, total kvarh,
partial kvarh, hour counters
- reset of all the above
mentioned variables in a
single command
Alarms
Working mode
“OR” or “AND” or
“OR+AND” functions (see
“Alarm parameter and logic”
page). The user can freely
program up to 16 total
alarms. (out1+out2).
The alarms
can be connected to any
variables available in the
table “List of the variables
that can be connected to”
The following resets are
available by means of the
configuration software:
- all the maximum/min values:
Reset
Softw are functions (cont.)