PCV Series
Proportional controller
Ratings from 15A to 90A @ 240 VAC
2-7 V DC or 2-10 V DC analog input range
For use with resistive loads only
PRODUCT SELECTION
Description
15 A
25 A
50 A
75 A
90 A
2-7 VDC Control
7PCV2415
7PCV2425
2-10 VDC Control
10PCV2415
10PCV2425
10PCV2450
10PCV2475
10PCV2490
OUTPUT SPECIFICATIONS (1)
Description
15 A
25 A
50 A
75 A
90 A
Operating Voltage (47-63Hz) [Vrms]
100-240
Transient Overvoltage [Vpk]
600
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
10
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/sec] (2)
200
Maximum Load Current (3) [Arms]
15
25
50
75
90
Minimum Load Current [Arms]
0.15
Maximum Surge Current (16.6ms) [Apk]
150
250
625
1000
1200
Maximum On-State Voltage Drop @ Rated Current [Vpk]
1.6
Maximum I t for Fusing (8.3 msec) [A sec]
94
260
1620
4150
6000
Minimum Power Factor (with Maximum Load)
0.5
INPUT SPECIFICATIONS (1)
Description
7PCV24xx
10PCV24xx
Control Voltage Range
2-7 VDC
2-10 VDC
Typical Input Current @ 5 VDC
4 mA
GENERAL SPECIFICATIONS
Description
Parameters
Dielectric Strength, Signal to Load (50/60Hz)
2500 Vrms
Dielectric Strength, Signal to Base
2500 Vrms
Ambient Operating Temperature Range
-30 to 80 °C
Ambient Storage Temperature Range
-40 to 125 °C
Weight (typical)
3.5 oz. (100g)
Encapsulation
Themaly Conductive Epoxy
Terminals
Screws and Saddle clamps Furnished, Unmounted
GENERAL NOTES
1) All param eters at 25°C unless otherwise specified.